Sinyal 4-20 mA: Cara Membaca Angka Arus Sebelum Menyalahkan Sensor
Foto: Pexels
IT Industri

4-20 mA Signal: How to Read Current Values Before Blaming the Sensor

The SCADA screen shows the tank level at 0 percent. Is the tank empty, or is the cable broken? At a signal of 0-20 mA, both conditions read 0 mA. At 4-20 mA, they are different, and the difference is immediately visible from the current reading.

4 mA is live zero

In a 4-20 mA loop, the transmitter adjusts the current according to its measurement value. 4 mA represents the lower limit of the range, 20 mA the upper limit, and the values in between are linear. Process zero is not sent as zero current.

The lower limit is not 0 mA for two reasons:

  • A broken cable becomes apparent. A current of 0 mA means an open circuit. If process zero is also sent as 0 mA, the control system cannot distinguish an empty tank from a broken cable.
  • The transmitter is powered from the loop itself. Many transmitters draw their power from the loop current. Since currents below 3.6 mA are used to indicate a fault, the transmitter circuit must be able to operate with a maximum current budget of 3 mA.

Formula to convert current to process value

Value = LRV + (I - 4) / 16 x (URV - LRV)

LRV is the value at 4 mA, URV is the value at 20 mA, and 16 is the width of the current range.

Example: an oven temperature transmitter is set to 100 °C at 4 mA and 500 °C at 20 mA. The current reads 12 mA, so the temperature is 100 + (8 / 16) x 400 = 300 °C.

The receiver typically reads the current as voltage across a load resistor, usually 250 ohms. At that resistor, 4 mA becomes 1 V and 20 mA becomes 5 V. A voltage of 3 V means 12 mA, right in the middle of the range.

Values outside 4-20 mA have meaning

The NAMUR NE 43 recommendation (July 26, 2021 edition) standardizes how transmitters indicate that they are faulty:

Current Meaning according to NE 43
3.8 to 20.5 mA measurement information
3.6 mA or less device fault
21 mA or more device fault

Not all transmitters are equipped with NAMUR levels. The Rosemount 3051 configuration sheet from Emerson distinguishes two types of outputs. Saturation means the process is out of the set range, while the transmitter is healthy. Alarm means the transmitter detects a severe fault in itself.

Option Low Saturation High Saturation Low Alarm High Alarm
Standard 3.90 mA 20.80 mA 3.725 mA 21.75 mA
NAMUR 3.80 mA 20.50 mA 3.575 mA 22.50 mA

Try comparing the two tables. The low alarm for the standard option is at 3.725 mA, above the 3.6 mA threshold. If the PLC input card only considers 3.6 mA and below as a fault, a standard transmitter that is malfunctioning will not be recognized as a device fault. The reading gets stuck in the gap between 3.6 and 3.8 mA.

A reading of 20.80 mA on a standard transmitter is also not a fault. It is saturation: the process has exceeded the URV.

HART rides on the same cable

Transmitters that support HART also send digital data over the 4-20 mA current. Its signals have two frequencies: 1200 Hz for bit 1 and 2200 Hz for bit 0, at a speed of 1200 baud. The process value itself changes below 20 Hz, so the receiver separates the two with a filter. The current reading remains readable as usual.

Checklist during commissioning

  1. Align the LRV and URV in the transmitter with the scale in the PLC or SCADA. A small difference here shifts all readings.
  2. Record the saturation and alarm levels of the transmitter: standard, NAMUR, or custom, as well as the direction of the alarm being high or low.
  3. Set the fault threshold on the input card according to that record, not according to habit.
  4. Provide different texts for saturation and fault on the HMI. Saturation is a process issue, while fault is an instrument technician issue.
  5. Test by measuring the voltage across the 250 ohm load resistor: 1 V means 4 mA, 5 V means 20 mA.

The alarm of this transmitter is different from the process alarm. The division of alarms, interlocks, and trips is discussed in the three-layer protection article for process plants. If you prefer to see the explanation directly, there is a short clip about 4-20 mA and 0-20 mA.

References