In a solar power plant proposal, the capacity of the panels and the capacity of the inverter are rarely the same. For example, a 100 kWp panel is paired with an 80 kW inverter. This is not a miscalculation. The comparison between the two is called the DC/AC ratio, or inverter loading ratio (ILR), and the figure is intentionally set to be greater than 1.
How to calculate it
DC/AC ratio = panel array capacity (kWp, DC side) divided by inverter capacity (kW, AC side). In the above example: 100 / 80 = 1.25.
Why not just 1? Panels almost never produce power equal to their kWp rating. That rating is measured under standard test conditions, while on the roof, panels are subjected to heat, dust, and changing sun angles. An inverter sized to the panel rating will more often operate far below its capacity.
A technical report by NREL (2020) notes two reasons why this ratio continues to rise from 1.2 to 1.3: the price of solar modules has decreased, and the capacity of AC connections to the grid is increasingly limited. Adding panels has become cheaper than enlarging the inverter.
The price: clipping
When panels produce power greater than the inverter's capacity, the excess is cut off. This is called clipping. The daily power graph becomes flattened at the peak of midday.
A study by Micheli et al. in the journal Renewable Energy (2024) modeled how much energy is clipped:
| DC/AC ratio | Modeled conditions | Clipped DC energy |
|---|---|---|
| 1.26 | system loss 15% | up to 0.2% |
| 1.34 | US national average, fixed panels | 1.4% |
| 1.34 | US national average, single-axis tracker | 0.6% |
| 1.45 | system loss 5% | 4% to 5% |
The figure of 1.34 is the median ILR of systems installed in the US in 2020, with the 20th and 80th percentiles at 1.26 and 1.45. Research from Sandia National Laboratories provides a similar picture: clipping can be significant for a moment at midday, but over the course of a year, it is among the smallest sources of loss. The total average loss in their simulation only shifted from 18.25% to 18.57% when the ratio was increased from 1.2 to 1.3.
Clipping decreases as panel age
The power output of panels decreases slightly each year. The Micheli study calculated that with a degradation of 0.75% per year and a ratio of 1.34, most tracking systems would no longer experience clipping after 20 years. For fixed panels, that point would only be reached around year 36.
This means that the energy lost in the early years is partially compensated in the latter half of the project's lifespan. A ratio that appears aggressive in the first year may feel just right in the fifteenth year.
The trap lies in simulation
A more common issue overlooked: simulation software tends to be overly optimistic for high ratios.
- NREL (2022) tested industry models on six systems and found that their energy forecasts were biased upwards, increasingly so as the ILR rose. For the range of 1.2 to 1.5, the bias was approximately 0% to 4%.
- Hourly weather data averages out spikes in sunlight that only last a few minutes. As a result, clipping is underestimated, around 1.5% at a ratio of 1.25 and 2.4% at a ratio of 1.50 according to the study summarized by Micheli et al.
So if a proposal uses a ratio above 1.3, ask about the resolution of the simulation data and whether sub-hourly clipping corrections have been applied.
Checklist before approving the ratio
- Recalculate the ratio yourself from the kWp of the panels and kW of the inverter in the proposal sheet.
- Match it with the inverter limits. The inverter data sheet lists the maximum DC power that can enter. The number of panels per string is also limited by voltage, which is discussed in the article number of panels per string and temperature correction.
- Request the clipping figure in writing as a percentage of annual energy, not just the word "small".
- Ask about the resolution of the weather data. Hourly or sub-hourly.
- Check the assumed performance ratio. NREL found that the optimal ratio heavily depends on this assumption, so the right ratio for one project may not be suitable for another project.
A brief explanation in video form is available at DC/AC ratio in solar power plants.
References
- Walker, A., Desai, J., Qusaibaty, A. (2020). Life-Cycle Cost and Optimization of PV Systems Based on Power Duration Curve with Variable Performance Ratio and Availability. NREL/TP-5C00-73850.
- Anderson, K. S., et al. (2022). The Effect of Inverter Loading Ratio on Energy Estimate Bias. NREL/CP-5K00-82812, IEEE PVSC 49.
- Micheli, L., Muller, M., Theristis, M., et al. (2024). Quantifying the impact of inverter clipping on photovoltaic performance and soiling losses. Renewable Energy 225, 120317.
- Azzolini, J. A., Reno, M. J. (2021). The Effects of Inverter Clipping and Curtailment-Inducing Grid Support Functions on PV Planning Decisions. Sandia National Laboratories, SAND2021-7638C.